Ventilation & humidity · Calculator

ERV / HRV Size Calculator

This calculator takes the continuous ventilation rate the house needs (usually from ASHRAE 62.2), the climate zone, whether summers are humid, whether the unit will also serve as bathroom exhaust with a boost mode, and the indoor temperature, and returns the rated unit size to look for, whether an ERV or an HRV suits the climate, the heat it recovers on the design day and the heat that would be lost with a plain exhaust fan.

Recovery ventilators are sold by rated airflow at a reference static pressure, and a unit chosen at exactly the required rate falls short once its filters load and its ducts add resistance. This calculator adds a margin for that, adds boost capacity if the unit replaces bathroom fans, and makes the ERV-or-HRV decision on the climate rather than on brand preference, with the reason stated.

ERV / HRV Size Calculator

Units
CFM

From the whole-house ventilation calculator (ASHRAE 62.2)

°F

Example result for the starting values. Enter your own and press Calculate.

Energy recovery ventilator

130 CFM HRV

for 90 CFM of continuous ventilation; recovers about 4,763 BTU/hr at 0 °F

Unit size
130 CFM
Type
HRV
Heat recovered at design
4,763 BTU/hr
  • Plain exhaust fan loses6,804 BTU/hr
  • HRV loses2,041 BTU/hr
Size, type and recovery
Continuous ventilation rate90 CFM
Rated capacity to look for130 CFM unit (113 CFM needed with margin)
Recommended typeHRV (cold, dry winters: an HRV recovers heat and lets excess indoor moisture leave, which a tight cold-climate house needs)
Climatezone 5 (cool), design 0 °F
Heat recovered at 0 °F (70% SRE)4,763 BTU/hr
Heat still lost at design2,041 BTU/hr
Same ventilation with a plain exhaust fan would lose6,804 BTU/hr
Fan power (typical)65 to 104 W at rated airflow
Show the arithmetic
  1. Rated capacity needed = 90 CFM × 1.25 margin = 113 CFM → next unit size 130 CFM
  2. Type: HRV because of cold, dry winters
  3. Heat recovered at the 0 °F design temperature = 90 × 1.08 × 70 °F × 70% = 4,763 BTU/hr
  4. Heat still lost with the ventilation air = 90 × 1.08 × 70 × 30% = 2,041 BTU/hr
  • In zones 5 to 7 an HRV core can frost at low outdoor temperatures; look for a unit with a defrost cycle, and expect the defrost to cut delivered ventilation on the coldest days.
  • Units are rated at a reference static pressure (often 0.4 in wc) and deliver less through long duct runs; the 1.25 margin covers filter loading and balancing. Have the installer balance supply and exhaust to within 10% so the house is neither pressurised nor depressurised. Recovery efficiency (SRE) varies from about 60 to 85% between models; 70% is typical.

Understanding your result

The headline is the rated unit size and the type, ERV or HRV, with the continuous ventilation rate and the heat recovered on the design day in the sub-line. The bars compare the heat a plain exhaust fan would lose with what the recovery ventilator still loses, the gap being the recovery. The stats give the unit size, the type and the heat recovered at design.

The table gives the reasoning for the type in plain words, the climate and design temperature the recovery is calculated at, the heat a plain exhaust fan would lose for the same airflow, and the typical electrical draw of the unit’s fans. The unit size includes a 25% margin over the continuous rate, and 50% more if you chose a boost mode for bathroom exhaust.

The continuous rate comes from the whole-house ventilation calculator. An HRV in a tight cold-climate house may leave it too dry or too humid depending on the household; the humidifier and dehumidifier calculators size the correction, and the bathroom exhaust fan calculator gives the rates a boost mode must meet.

How we calculate this

rated capacity needed = ventilation rate × 1.25 margin (× 1.5 more with a bathroom boost mode) unit size = next rated size sold at or above that (70, 100, 130, 150, 200, 250, 300 CFM) heat in the ventilation air = CFM × 1.08 × (indoor temperature − design temperature) heat recovered = heat in the ventilation air × sensible recovery efficiency (70%) heat still lost = heat in the ventilation air × (1 − 0.70)

The 1.08 is the sensible heat factor for standard air (BTU per hour per CFM per °F). The design temperature is the typical 99% winter design temperature for the climate zone used across the site. The 70% sensible recovery efficiency is typical of residential units tested under the Home Ventilating Institute’s ERV and HRV procedures, whose certified ratings range from about 55 to 85%; use the rating of the model you choose for a final figure. The type recommendation follows the usual guidance from the US Department of Energy and the manufacturers: HRV where winters are cold and dry and summers are not humid, ERV where summers are humid or the climate is warm. The ventilation rates are on the ventilation and exhaust minimums page.

The assumptions behind the numbers

Assumption Value Where it comes from
Margin over the ventilation rate 25% Filter loading, duct static and balancing; typical installer practice
Boost factor 1.5 × To meet bathroom intermittent exhaust rates on boost
Unit sizes 70 to 300 CFM Residential ERVs and HRVs sold in North America
Sensible recovery efficiency 70% Typical HVI-certified residential units (55 to 85% range)
Design temperatures 50 to −20 °F by zone Typical 99% heating design temperatures, rounded
Fan power 0.5 to 0.8 W per CFM Typical residential ERV/HRV fan efficacy

Assumptions last reviewed October 8, 2026.

The calculator does not model latent (moisture) recovery, which an ERV adds and which matters most in humid summers, the loss of fresh air during defrost cycles, the static pressure of your actual ducts or the fan curve of a particular unit. The guide to whole-house ventilation compares exhaust-only, supply-only and balanced strategies, and the guide to humidity and comfort explains how each affects indoor humidity.

Two worked examples

A cold-climate house

90 CFM of continuous ventilation in zone 5 (0 °F design), summers not especially humid, no boost, 70 °F indoors.

  • Rated capacity needed: 90 × 1.25 = 113 CFM → 130 CFM unit
  • Type: HRV, for cold, dry winters
  • Heat in the ventilation air: 90 × 1.08 × 70 = 6,804 BTU/hr
  • Recovered at 70%: 4,763 BTU/hr; still lost 2,041 BTU/hr

On the design night the HRV saves about 4,800 BTU per hour of heat, a little under a third of a ton of heating, for about 65 to 100 watts of fan power. The note reminds the installer to choose a unit with defrost, because at 0 °F an HRV core frosts.

A humid warm-climate house with boost

60 CFM continuous in zone 2 (35 °F design), humid summers, boost mode for the bathrooms, 75 °F indoors.

  • Rated capacity needed: 60 × 1.25 × 1.5 = 113 CFM → 130 CFM unit
  • Type: ERV, for humid summers
  • Heat in the ventilation air at 35 °F: 60 × 1.08 × 40 = 2,592 BTU/hr; recovered 1,814

In a warm climate the winter heat recovery is modest; the ERV earns its place in summer, when it removes part of the moisture from incoming air before it reaches the air conditioner. The boost mode lets it replace two bathroom fans, provided each bathroom has a boost switch and an exhaust pickup.

Where to find your inputs

Ventilation rate. From the whole-house ventilation calculator, or the mechanical ventilation rate on the house’s energy compliance documents.

Climate zone. By county on the DOE map, as for the sizing calculators.

Humid summers. If outdoor dew points in July are often above 65 °F (sticky air), tick the box.

Boost. Tick it only if the unit’s exhaust picks up from the bathrooms and is controlled from them.

Common mistakes

  • Sizing to exactly the ventilation rate. Filters load and ducts add resistance; allow a margin.
  • Choosing by brand instead of climate. HRV for cold and dry, ERV for humid or warm.
  • Kitchen exhaust through the ventilator. Grease fouls the core; use a range hood.
  • Unbalanced airflow. An installer should measure and balance supply and exhaust.
  • No defrost in a cold climate. An HRV core freezes below about 23 °F without it.
  • Never cleaning the filters and core. Clogged filters cut airflow and recovery; check them every few months.

Questions people ask

What size ERV or HRV do I need?
One whose rated airflow, at the static pressure of your duct system, covers the ASHRAE 62.2 rate with about 25% to spare. A 2,000 sq ft three-bedroom house needs 90 CFM continuous, so a unit rated about 113 CFM or more, which in practice is a 130 CFM unit. If the unit also replaces bathroom exhaust fans on a boost setting, size for about 1.5 times the continuous rate with the margin, about 170 CFM for the same house.
What is the difference between an ERV and an HRV?
Both bring in fresh air and exhaust stale air through a heat exchanger core, recovering 60 to 85% of the heat. An HRV's core transfers only heat. An ERV's core also transfers moisture, so in winter it keeps some indoor humidity in and in summer it keeps some outdoor humidity out. An HRV suits cold climates where a tight house has too much winter moisture; an ERV suits humid climates and houses that get too dry in winter.
Should I get an ERV or an HRV in a cold climate?
Usually an HRV in zones 5 to 7 when the house is tight and winter condensation on windows is the problem, because the HRV lets excess indoor moisture leave. If the house is dry in winter, or summers are humid as in Minneapolis or Boston, a modern ERV is the better fit. Both need a defrost strategy below about 23 °F outdoors, which briefly cuts the fresh air delivered.
How much energy does an HRV save?
It recovers 60 to 85% of the heat that ventilation air would otherwise carry out. For 90 CFM of ventilation at 70 °F indoors and 0 °F outdoors, the air carries out about 6,800 BTU per hour; an HRV at 70% sensible recovery returns about 4,760 of that, leaving 2,040. Over a heating season in a cold climate that is several hundred dollars of heat, against the 50 to 100 watts the unit's two fans use.
Can an ERV replace bathroom exhaust fans?
Yes, if it has a boost mode controlled from each bathroom and its exhaust ducts pick up from the bathrooms. ASHRAE 62.2 allows the bathroom exhaust requirement (50 CFM intermittent or 20 continuous) to be met by the ventilator's exhaust when it can deliver those rates, which is why boost-capable units are sized about 50% above the continuous rate. Kitchen exhaust should still go through a range hood, never through an ERV, because grease fouls the core.
Does an ERV or HRV need its own ducts?
Best results come from dedicated ducts that supply fresh air to bedrooms and living areas and exhaust from bathrooms and the kitchen area. A simplified installation ties into the furnace return and runs the furnace blower, which is cheaper to install but uses more fan energy and mixes the fresh air less evenly. Either way the installer should balance supply and exhaust to within 10% so the house is neither pressurised nor depressurised.
Embed this calculator on your site

Paste the code into any page. It is free to use; the only thing we ask is that the credit link under the calculator stays.

See all calculators: embed