Planning & comfort · Calculator

Generator Size for HVAC Calculator

This calculator takes the air conditioner or heat pump's size in tons, or its nameplate rated load amps and locked rotor amps, whether a soft-start kit is fitted, the blower's watts, any heat strips to run, the other loads running at the same time and a margin, and returns the running watts, the peak when the compressor starts, and the generator size to buy.

The compressor's starting surge, three to five times its running power for a fraction of a second, is what sizes a generator for air conditioning, and it is the figure most generator calculators leave out or guess. This calculator uses the locked rotor amps from the nameplate when you have them, adds the other loads that will be running at the moment the compressor starts, and shows what a soft-start kit does to the answer.

Generator Size for HVAC Calculator

Units
Air conditioner data from
tons
W

400 to 800 W for a standard blower; 100 to 500 W variable speed

kW

Leave at 0 unless the generator must run them (they are large)

W

Refrigerator 700, sump pump 800, lights 300, well pump 1,500, electronics 300

%

Example result for the starting values. Enter your own and press Calculate.

Generator size

20 kW

Running about 6.1 kW, peak about 16.6 kW when the compressor starts

Running
6.1 kW
Peak at start
16.6 kW
Generator
20 kW
  • Running6,110 W
  • Peak at start16,640 W
Loads and surge
AC running watts3,510 W
AC starting watts14,040 W
Blower600 W
Heat strips0 W
Other loads2,000 W
Total running6,110 W
Peak when the compressor starts16,640 W
Needed with 10% margin18,304 W
Generator size20 kW
Show the arithmetic
  1. AC running ≈ 3 tons × 1170 W = 3,510 W; starting surge ≈ × 4 = 14,040 W
  2. Running total = 3,510 + 600 blower + 0 strips + 2,000 other = 6,110 W
  3. Peak at compressor start = 2,600 + 14,040 = 16,640 W; with 10% margin = 18,304 W → 20 kW generator
  • A soft-start kit would cut the starting surge to about 7,196 W and could drop the generator a size or more; kits cost a few hundred dollars installed.
  • The starting surge is estimated at four times running watts; the LRA on the outdoor unit's nameplate gives the real figure, and some compressors need less, some more.
  • Portable generator ratings are often given in starting and running watts; standby generators in kW, often derated for natural gas versus propane. A transfer switch or interlock is required by code, and the generator, transfer switch and connections must be installed by a licensed electrician. Never run a generator indoors or in a garage: carbon monoxide kills.

Understanding your result

The headline is the generator size, with the running load and the peak at compressor start in the sub-line. The bars compare the two. The table shows the air conditioner’s running and starting watts, the blower, heat strips and other loads, the total running, the peak when the compressor starts with everything else already running, the requirement with your margin, and the size.

The peak at start is what the generator must deliver for a moment, and it is usually far larger than the running total. That gap is why a soft start matters: the notes show what it would do to the result if you have not ticked it.

The running watts of the air conditioner are the same figure the AC running cost calculator uses to price an hour of cooling, and the HVAC running cost calculator does it for a heat pump. Sizing the air conditioner itself is the job of the central AC size calculator; a heat pump’s need for strips, which drives generator size in winter, comes from the heat pump size calculator.

How we calculate this

from tons: AC running ≈ tons × 1,170 W; starting ≈ running × 4 from nameplate: AC running = RLA × 240 V + fan watts; starting = LRA × 240 V soft start: starting = running + (starting − running) × 0.35 running total = AC running + blower + heat strips + other loads peak at start = running total − AC running + AC starting generator = next size at or above the larger of the two × (1 + margin)

The running watts per ton correspond to about 3,500 W for a typical 3-ton unit of 13 to 15 SEER2; the starting multiplier of four is the middle of the usual three to five times running power when the locked rotor amps are not known. Soft-start manufacturers claim a 60 to 70% reduction in starting current; the calculator uses 65%. Standby generator sizes from 5 to 30 kW are the residential range. The electrical background of efficiency ratings is on the efficiency ratings table, and watts and BTU are converted on the unit conversions page.

The assumptions behind the numbers

Assumption Value Where it comes from
AC running watts 1,170 W per ton Our estimate for 13 to 15 SEER2 units (3 tons ≈ 3,500 W)
Starting surge without nameplate 4 × running Middle of the usual 3 to 5 × range
Nameplate surge LRA × 240 V Locked rotor amps from the outdoor unit nameplate
Soft-start reduction 65% of the surge Manufacturer claims of 60 to 70%
Blower 600 W Typical PSC blower; variable speed 100 to 500 W
Other loads 2,000 W Refrigerator, sump pump, lights and electronics running together
Margin 10% Common sizing practice

Assumptions last reviewed October 8, 2026.

The calculator does not derate the generator for fuel (natural gas output is often 10 to 20% below the propane rating), altitude or temperature, does not model voltage dip tolerance, which varies by compressor, and assumes 240 V single-phase. A licensed electrician’s load calculation is the standard for the final size, and the generator, transfer switch and connections must be installed by one. The guide to heat pumps in cold climates covers the strip heat that makes winter backup hard, and the guide to what HVAC installations cost covers the equipment side.

Two worked examples

A 3-ton air conditioner without a soft start

3 tons, no soft start, 600 W blower, no strips, 2,000 W of other loads, 10% margin.

  • AC running: 3 × 1,170 = 3,510 W; starting ≈ 14,040 W
  • Running total: 3,510 + 600 + 2,000 = 6,110 W
  • Peak at start: 2,600 + 14,040 = 16,640 W; with margin 18,304 W
  • Generator: 20 kW

The house needs only about 6 kW to run, but 16.6 kW for the instant the compressor starts. The note says a soft-start kit would bring the surge to about 7,200 W and the generator down a size or more.

The same size from the nameplate, with a soft start

RLA 14 A, LRA 75 A, 200 W outdoor fan, soft start fitted, 600 W blower, 1,500 W of other loads, 10% margin.

  • AC running: 14 × 240 + 200 = 3,560 W
  • Starting: 75 × 240 = 18,000 W; with soft start 3,560 + 14,440 × 0.35 = 8,614 W
  • Running total 5,660 W; peak at start 2,100 + 8,614 = 10,714 W; with margin 11,785 W
  • Generator: 12 kW

The soft start saves the difference between a 20 kW and a 12 kW standby generator, several thousand dollars, for a few hundred dollars of kit. Using the nameplate’s real LRA rather than the rule of thumb also makes the answer firmer.

Where to find your inputs

RLA and LRA. On the nameplate of the outdoor unit, usually on a side panel; “RLA” or “RL” and “LRA” or “LR” next to the compressor line.

Blower watts. From the furnace or air handler’s specifications, or about 400 to 800 W for a standard blower.

Other loads. Add the running watts of what must run together: refrigerator about 700 W, sump pump 800, well pump 1,500, lights and electronics a few hundred.

Common mistakes

  • Sizing on running watts. The compressor’s start decides the size.
  • Starting everything at once. The calculator assumes the compressor starts with other loads already running, which is the realistic worst case.
  • Back-feeding through an outlet. It is illegal and can kill line workers; use a transfer switch or interlock.
  • Planning to run heat strips. They need a very large generator; back up a gas furnace or a cold-climate heat pump instead.
  • Ignoring the fuel derating. A generator on natural gas often delivers less than its propane rating.
  • Running a generator in a garage. Carbon monoxide is deadly; keep it outside, away from doors and windows.

Questions people ask

What size generator do I need to run a 3-ton air conditioner?
A 3-ton air conditioner draws about 3,500 watts running, but its compressor needs three to five times that for a moment to start. With a 600 W blower and 2,000 W of household basics running, the peak when the compressor starts is about 16.6 kW, so a 20 kW standby generator with a 10% margin. With a soft-start kit and the nameplate figures of a typical 3-ton unit (14 A running, 75 A locked rotor), about 12 kW is enough.
What are RLA and LRA?
Rated load amps (RLA) is the current the compressor draws running at its rated conditions; locked rotor amps (LRA) is the current it draws for the fraction of a second when it starts, before the motor turns. Both are on the outdoor unit's nameplate. Multiplied by 240 volts, RLA gives the running watts and LRA the starting surge; a 75 A LRA is an 18,000 W surge, which is why a generator that can run the unit may not start it.
Does a soft start really reduce the generator size?
Yes, often by a size or two. A soft-start kit ramps the compressor's starting current over a fraction of a second, cutting the surge by about 60 to 70% according to manufacturers. On a typical 3-ton unit that brings the starting draw from about 18,000 W to under 9,000 W, the difference between a 20 kW and a 12 kW generator. Kits cost a few hundred dollars installed and are a common addition when a generator is planned.
Can a portable generator run central air?
Some can run a small central air conditioner, especially with a soft-start kit, if their starting watts exceed the compressor's surge plus the other loads. A typical 7,500 to 9,500 W portable generator can start a 2-ton unit with a soft start and little else running. It must connect through a transfer switch or a code-approved interlock installed by a licensed electrician, never by back-feeding an outlet.
Can a generator run electric heat strips?
Only a large one. Heat strips are 5 to 20 kW of resistance heat, often the largest load in the house, so running a heat pump with 10 kW of strips adds 10,000 W to the running total and usually pushes the generator to 22 kW or more. Houses that want generator-backed heat are better served by a gas furnace, which needs only its blower, or a cold-climate heat pump that needs little strip heat.
Should the generator be sized for everything at once?
Not necessarily. Load-management modules and smart transfer switches can shed loads such as the air conditioner, the water heater or the dryer when the generator nears capacity, so a smaller generator covers the essentials and runs the air conditioner when other loads are off. The calculator sizes for the loads you enter running together with the compressor's start, which is the safe case.
Embed this calculator on your site

Paste the code into any page. It is free to use; the only thing we ask is that the credit link under the calculator stays.

See all calculators: embed