Duct and airflow calculators

CFM per room and per ton, duct sizes, velocity, return grilles, registers, equivalent lengths, air changes and exhaust fans.

Airflow is the half of an HVAC system that nobody sizes. The equipment arrives with a rating, but the ducts that carry its air are often whatever fitted the joists, and a 3-ton system pushing air through ducts sized for 2 tons loses capacity, makes noise and freezes its coil. The calculators here cover the whole air path: how much air each room needs, how big the duct must be to carry it at a sensible friction rate, how fast the air moves, how large the return grilles and registers have to be, and how much resistance the fittings add.

The method behind them is the equal-friction approach used in residential design: pick a friction rate, typically 0.08 to 0.10 inches of water per 100 feet of duct, and size every run so it loses pressure at that rate. ACCA Manual D is the full procedure and includes the equipment's available static pressure, which these calculators ask you to check rather than assume.

9 calculators

Guides for this topic

Questions people ask

How many CFM per ton does a system need?
400 CFM per ton is the usual design figure, giving 800 CFM for a 2-ton system and 1,200 CFM for 3 tons. Humid climates run 350 CFM per ton for better dehumidification; hot dry climates can run 450. The number matters because every duct, grille and register downstream is sized from it, and a system starved of air loses capacity and efficiency.
What size duct do I need for 400 CFM?
At a friction rate of 0.1 inches of water per 100 ft, 400 CFM calls for a 10-inch round duct, with air moving at about 730 feet per minute. The rectangular equivalents are about 8 × 12 or 6 × 16 inches. A 9-inch duct would carry the same air at 900 FPM and a higher friction rate, which is noisier and costs fan energy; this is why the duct size calculator shows velocity next to the diameter.
How big should a return air grille be?
Size returns for a face velocity of 300 to 500 feet per minute so they stay quiet; many designers use 400. A 3-ton system moving 1,200 CFM needs about 3 sq ft of free area at 400 FPM, and because a stamped grille is only about 70% open, that means roughly 4.3 sq ft of grille, for example two 20 × 20 inch returns or one 24 × 30. Undersized returns are the most common duct fault in houses.
What is the maximum velocity for residential ducts?
Common residential limits are 700 to 900 feet per minute in supply trunks, 600 to 700 in branch runs, and 500 to 700 in returns; registers and grilles are kept lower still so they do not whistle. Commercial systems run faster because noise is tolerated and ducts are stiffer. The duct velocity calculator compares your duct to these limits.
How many air changes per hour should a bedroom have?
Comfort and code targets differ. For whole-house ventilation, ASHRAE 62.2 works out to roughly 0.35 air changes per hour of outdoor air in a typical house. Bathrooms are often sized for 8 air changes per hour of exhaust. A conditioned-air supply of 4 to 6 air changes per hour is typical for a bedroom served by a central system. The air changes calculator converts between CFM and ACH for any room.

More calculators on our other sites

  • Drywalls Calculator

    Sheets, screws, joint compound, tape, corner bead, studs, soundproofing and what hanging and finishing drywall costs.

  • Floorings Calculator

    How much tile, wood, vinyl, carpet, underlayment and trim a floor needs, and what it costs.

  • Paints Calculator

    How much paint, primer, stain and wallpaper a job needs, and what it costs.